The organization of the FSA Team and the criteria for selection of team members
shall be well defined. To increase objectivity, the FSA team shall have a defined
level of independency with respect to the actual project team. At least the FSA team
leader shall be from an independent organization. Depending on the organization of
the company and the internal skills within the company, the company may use their
own resources to meet requirements for an independent organization.
Functional Safety Assessment Planning
The stages in the safety lifecycle at which the Functional Safety Assessment
activities are to be carried out shall be identified during safety planning.
The number, size and scope of FSA should be defined upon specific circumstances
that shall be defined. The circumstances and the method to select FSA scope shall
be defined.
Functional Safety Assessment - Minimum Requirements
One Functional Safety Assessment, as a minimum, shall be carried out to make sure
that the hazards arising from the process and its associated equipment are properly
controlled. It shall be carried out prior to the startup of the process and shall confirm
that:
• Hazard and risk assessment has been carried out, and recommendations are
implemented and resolved
• Project design procedures are properly implemented
• The SIS is in accordance with the safety requirement specification
• The operation, maintenance and emergency procedures to the SIS are in place
• The validation planning is appropriate and validation activities are completed
• The training activities of maintenance and operating personnel are completed