| US$85.00-550.00 | 1 Set (MOQ) |
| Model | VT 6KVA | VT 6KS | VT 10KVA | VT 10KS | |
| Rated Power | 6kVA/5.4kW | 10kVA/9kW | |||
| Input | Voltage Range | 120-275Vac 1P2W+G | |||
| Working Frequency Range | 40-70Hz (settable) | ||||
| Input Power Factor | ≥0.99 | ||||
| Output | Rated Voltage and Accuracy | 220Vac(1±1%) 1P2W+G | |||
| Output Frequency | 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery) | ||||
| Rated Current | 27A | 45A | |||
| Output Power Factor | 0.9 | ||||
| Output Harmonic Wave | ≤3% (Full R load) | ||||
| Crest Factor | 3 | :1 | |||
| Output Overload | 105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min; 125%±5%<Load≤135%±5%: Convert to bypass output and alarm after 30s; Load>135%±5%: Convert to bypass output and alarm after 300ms. | ||||
| Conversion time between Mains Power and Battery | 0ms | ||||
| Efficiency | >92% | ||||
| Battery | Rated Voltage | 192Vdc | |||
| Quantity | 16 | ||||
| Charging Current | 1A | 5.5A | 1A | 5.5A | |
| Dimension (LxWxH) mm | 533x260x560 | 425x190x328 | 533x260x560 | 533x260x501 | |
| Weight | 55kg | 12.2kg | 62kg | 21kg | |
| Working Temperature | 0ºC-40ºC | ||||
| Working Humidity | 20%-95% (non-condensing) | ||||
| Noise | ≤55dB | ||||