| High Frequency UPS | ||||||||||||
| Model | AF1K | AF1KL | AF2K | AF2KL | AF3K | AF3KL | AF6K | AF6KL | AF10K | AF10KL | ||
| Capacity | 1KVA/800W | 2KVA/1.6KW | 3KVA/2.4KW | 6KVA/4.8KW | 10KVA/8KW | |||||||
| Battery voltage | 12V7AH*2 | 36VDC | 12V7AH*4 | 72VDC | 12V7AH*6 | 96VDC | 12V7AH*16 | 192VDC | 12V7AH*16 | 192VDC | ||
| Size, D*W*H(mm) | 350X144X230 | 350X144X230 | 425X190X328 | 425X190X328 | 425X190X328 | 425x190X328 | 533X260X560 | 425X190X328 | 533X260x560 | 533X260x560 | ||
| Net weight(kgs) | 9 | 6 | 18.4 | 9 | 23.4 | 10 | 55 | 12.2 | 62 | 21 | ||
| Input | ||||||||||||
| Input voltage | 90V-285Vac | 120-275VAC | ||||||||||
| Frequency range | 40Hz-70Hz | 46-54Hz or 56-64Hz | ||||||||||
| Phase | Single phase with ground | |||||||||||
| Power factor | ≥0.99 @ 100% Load | |||||||||||
| Output | ||||||||||||
| Output voltage | 100/110/115/120/127 VAC or 200/208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
| AC voltage regulation | +-1% | |||||||||||
| Frequency range(synchronize range) | 40-46Hz or 54-60Hz | 46-54Hz or 56-64Hz | ||||||||||
| Frequency range (batt. mode) | 50Hz+-0.25Hz or 60Hz+-0.3Hz | 50Hz or 60Hz+-0.1Hz | ||||||||||
| Current crest ratio | 3:01 | |||||||||||
| Output current | 4.5A 9.1A | 9.1A | 13.6A | 27A | 45A | |||||||
| Harmonic distortion | ≤3% THD (Linear load) ≤6% THD (Non-linear load) | ≤3% THD (Linear load) ≤5% THD (Non-linear load) | ||||||||||
| Overload | 105%+-5%<Load≤125%+-5%: after 50secs turn to bypass and alarm; 125%+-5%<Load≤150%+-5%: after 25secs turn to bypass and alarm; load>150%+-5%: after 300ms turn to bypass and alarm. | 105%+-5%<Load≤125%+-5%: after 1mins turn to bypass and alarm; 125%+-5%<Load≤135%+-5%: after 30secs turn to bypassand alarm; load>135%+-5%: after 300ms turn to bypass and alarm. | ||||||||||
| Transfer time /AC mode to batt. mode | Zero | |||||||||||
| Waveform(batt. mode) | Pure Sinewave | |||||||||||
| Efficiency | ||||||||||||
| Battery mode | 85% | 92% | 92% | |||||||||
| Battery | ||||||||||||
| Battery type | 12V/7 Ah | Depending on applications | 12V/7 Ah | Depending on applications | 12V/7 Ah | Depending on applications | 12V/7 Ah | Depending on applications | 12V/7 Ah | Depending on applications | ||
| Battery numbers | 2 | 4 | 6 | 16 | 16 | |||||||
| Recharge time | 8 hours recover to 90% capacity | 9 hours recover to 90% capacity | ||||||||||
| Charging current | 1A | 6.5A | 1A | 5.5A | 1A | 5.5A | 1A | 5.5A | 1A | 5.5A | ||
| Environment | ||||||||||||
| Operation humidity | 20-90% RH @ 0-40ºC Non-condensing | 0-95% RH @ 0-50ºC Non-condensing | 0-95% RH @ 0-40ºC Non-condensing | |||||||||
| Noise level | Less than 50dBA @ 1 Meter | Less than 55dBA @ 1 Meter | Less than 58dBA @ 1 Meter | |||||||||
| Management | ||||||||||||
| Smart RS-232 | Support windows2000/2003/XP/Vista/2008,Windows7/8,Linux,Unix and MAC | |||||||||||
| Optional SNMP | Power management from SNMP management and web browser | |||||||||||